RFIs
4 requests on file. Average time-to-draft: 31 seconds.
RFI-118sentto HOK
Medical gas outlet type at OR Suite 3
Drawings show DISS outlets; spec calls for Ohmeda quick-connect. Please confirm.
Created May 13, 2026
RFI-117answeredto HOK
Imaging suite shielding — coverage extent
Level 1, Imaging Suite
Lead shielding shown on plan stops at door opening, but spec section 27 10 00 calls for shielding to extend 6" into adjacent wall studs. Please confirm extent of shielding.
Created May 9, 2026
RFI-116closedto HOK
Patient room headwall — outlet quantity discrepancy
Levels 4-6, typical patient rooms
Architectural shows 4 medical gas outlets per headwall; mechanical shows 5. Please clarify final count.
Created May 4, 2026
RFI-115answeredto HOK
Roof access ladder location at Penthouse
Plan and section disagree on roof access ladder location. Please confirm.
Created Apr 28, 2026